CLEARANCES TO COMBUSTIBLES (UL AND ULC)
Page 6
FLOOR PROTECTOR: Floor
protector must be noncombustible
material or equivalent, extending
beneath heater and to the front/
sides/rear as indicated.
NOTE: A 3/8 (10mm) minimum
thickness tile or equivalent is
recommended, but not required.
G
8
Minimum clearances to Combustible Materials (in inches and millimeters) for Quadra-Fire 4300 Series
Chimney &
Installation Clearance Connector A B C D E F G
Residential Standard Note 1 19(483) 32(813) 21(533) 16(406) 22(559) 12(305) 52(1321)
Residential/Mobile Home Reduced Note 2 10(254) 27(586) 18(457) 7(178) 17(432) 9(229) 52(1321)
Alcove Standard Note 2 & 3 10(254) 27(586) 18(457) 7(178) 17(432) 9(229) 52(1321)
Minimum clearances to Combustible Materials (in inches and millimeters) with top shield
Minimum clearances to Combustible Materials (in inches and millimeters) for Quadra-Fire 4300 Step Top
Chimney &
Installation Clearance Connector A B C D E F G
Residential Standard Note 1 19(483) 32(813) 18(457) 16(406) 22(559) 9(229) 52(1321)
Residential/Mobile Home Reduced Note 2 10(254) 27(686) 12(305) 7(178) 17(432) 3(76) 52(1321)
Alcove Standard Note 2 & 3 10(254) 27(686) 12(305) 7(178) 17(432) 3(76) 52(1321)
Minimum clearances to Combustible Materials (in inches and millimeters) with extended top shield
Chimney &
Installation Clearances Connector A B C D E F G
Residential Standard Note 1 15(381) 24(610) 18(457) 12(305) 14(356) 9(229) 52(1321)
Residential/Mobile Home Reduced Note 2 10(254) 24(610) 12(305) 7(178) 14(356) 3(76) 38(966)
Alcove Standard Note 2 & 3 10(254) 24(610) 12(305) 7(178) 14(356) 3(76) 38(966)
Note 1: 6 (152mm) diameter single wall, minimum 24 MSG black or blued steel connector pipe with a listed factory-built type HT
chimney suitable for use with solid fuels or a masonry chimney.
Note 2: 6 (152mm) diameter double wall insulated connector pipe with listed factory-built type HT chimney or a masonry chimney.
(Mobile home venting system must be equipped with a rain cap and spark arrestor.) For installations with a preexisting class A
chimney system, a listed stainless steel chimney liner should be installed, or the existing chimney examined by a chimney sweep for
acceptable further use.
Note 3: Alcove specifications: Maximum depth of alcove shall be no more than 48 (1219mm). For additional alcove information
and clearances, refer to clearances to combustibles above.
NOTE: Unit is approved for use with listed double wall air-insulated chimney connector or elbows.
When locating your stove consider safety, convenience, traffic flow, and the fact that the stove will need a chimney and chimney
connector.
FLOOR PROTECTION: Floor protector must be noncombustible material, extending beneath heater and to the front/sides/rear as
indicated.
NOTE: A 3/8 (10mm) minimum thickness tile or equivalent is recommended, but not required.
NFPA 211: Use a noncombustible material with 1 (25mm) ventilated air space to reduce clearances. However, this is not to exceed
50% of Quadra-Fires specified clearances.
NOTE: Must follow NFPA 211 spacing and materials to qualify. It is also subject to local jurisdiction.
AVOID FIRE: Maintain the designated clearances to combustibles. Insulation must not touch the chimney. You must maintain the
designated air space clearance around the chimney. This space around a chimney is necessary to allow natural heat removal from the
area. Insulation in this space will cause a heat buildup, which may ignite wood framing.